Chapter 8: Using the Command Line Interface
509
Option
Description
lastKnownState Restores all outlets to the previous status before
powering down the PX3TS device when the PDU
powers up again.
Note: This feature does NOT take effect and cannot be configured on a
PX3TS device after the outlet relay is set to the "Latching" mode. See
PX3TS Latching Relay Behavior
(on page 182).
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation
for all outlets.
config:#
pdu cyclingPowerOffPeriod <timing>
Variables:
<timing> is the time of the cycling power-off period in seconds,
which is an integer between 0 and 3600, or
pduDefined for following
the PDU-defined timing.
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:#
pdu inrushGuardDelay <timing>
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...