Chapter 4: Connecting External Equipment (Optional)
73
Daisy-Chain Limitations of Composite Asset Strips
There are some limitations when daisy chaining composite asset strips
"AMS-Mx-Z," where x is a number.
The maximum cable length between composite asset strips is 2
meters, but the total cable length cannot exceed 10 meters.
The maximum number of composite asset strips that can be daisy
chained depends on the Raritan product you purchased.
It is NOT supported to hot swap or hot plug any AMS-Mx-Z in a
composite asset strip chain that has been connected to Raritan's
PDU (or PMC). Therefore, first disconnect the chain from the device
when you need to swap or add any AMS-Mx-Z to the chain.
Raritan devices
Maximum strips per chain
EMX2-111,
PX2 PDUs,
BCM1 (NOT BCM2
series)
Up to 4 composite asset strips
are supported.
EMX2-888,
PX3 PDUs,
PX3TS transfer
switches
PMC (BCM2 series)
Up to 6 composite asset strips
are supported.
Note for PX3TS-iX7 only: In case you hot swap or hot plug any AMS-Mx-Z
in a chain, causing the FEATURE port of the PX3TS-iX7 to malfunction,
you can power cycle or reset the PX3TS to restore the FEATURE port.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...