Chapter 8: Using the Command Line Interface
621
Note: To specify the Z coordinate using the rack units, see
Setting
the Z Coordinate Format for Environmental Sensors
(on page
<description> is a sentence or paragraph comprising up to 64 ASCII
printable characters, and it must be enclosed in quotes.
Example - Actuator Naming
The following command assigns the name "Door lock" to the actuator
whose ID number is 9.
config:#
actuator 9 name "Door lock"
Server Reachability Configuration Commands
You can use the CLI to add or delete an IT device, such as a server, from
the server reachability list, or modify the settings for a monitored IT
device. A server reachability configuration command begins with
serverReachability.
Adding a Monitored Device
This command adds a new IT device to the server reachability list.
config:#
serverReachability add <IP_host> <enable> <succ_ping>
<fail_ping> <succ_wait> <fail_wait> <resume> <disable_count>
Variables:
<IP_host> is the IP address or host name of the IT device that you
want to add.
<enable> is one of the options:
true or false.
Option
Description
true
Enables the ping monitoring feature for the newly
added device.
false
Disables the ping monitoring feature for the newly
added device.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...