Chapter 6: Using the Web Interface
174
Power Quality Settings
Inlet power quality state (normal/warning/critical) is derived from the
inlet's voltage and frequency quality - whichever is lower. If voltage or
frequency is critical, power quality is critical. If either is warning, quality
is warning. When both are normal, power quality is normal.
PX3TS transfers to standby operation when preferred inlet power quality
goes critical and retransfers to normal operation when power quality
returns to normal. The warning state does not cause transfers and is
intended as an early warning indication of a possible problem.
When quality goes from better to worse, the state change is said to
assert. You configure how long the quality must remain in the worse
state before the state change actually occurs. When quality goes from
worse to better, the state change is said to deassert. You configure the
hysteresis - how much the quality must be better than the threshold -
before the state change occurs.
To configure power quality thresholds for both inlets:
1.
Choose Transfer Switch > Edit Power Quality Parameters. See
Transfer Switch
(on page 162).
2.
Both voltage and frequency thresholds are shown onscreen. The
ways to configure them are identical.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...