Chapter 6: Using the Web Interface
172
Data
Description
Fuse Status
Indicates whether each fuse works properly.
open: The fuse works fine.
closed: The fuse is blown or malfunctions.
When this occurs, replace the fuse. See
Fuses for the Inlet Transfer Switch
(on
page 133).
unavailable: The PX3TS cannot determine the
fuse's status. For example, "unavailable" is
shown when there is no inlet power available.
MOV Status
Indicates whether each inlet's MOV surge
protector works properly.
If fine, "OK" is displayed.
Otherwise, "fault" is displayed. In this case,
contact Raritan for Return Merchandize
Authorization (RMA) to fix the issue.
+12V Supply
Status
The transfer switch receives DC 12V power from
either inlet. The transfer switch works fine as
long as one of the 12V power supplies works
properly.
This +12V status field indicates whether each
inlet's 12V power supply to the transfer switch
functions properly.
If fine, "OK" is displayed.
Otherwise, "fault" is displayed. In this case,
contact Raritan for Return Merchandize
Authorization (RMA) to fix the issue.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...