Chapter 4: Connecting External Equipment (Optional)
51
The following procedure illustrates a DPX2 sensor cable with three head
connectors. Your sensor cable may have fewer head connectors.
Warning: If there are free head connectors between a DPX2 sensor
cable's RJ-12 connector and the final attached DPX2 sensor package,
the sensor packages following the free head connector(s) on the same
cable do NOT work properly. Therefore, always occupy all head
connectors prior to the final sensor package with a DPX2 sensor
package.
To connect DPX2 sensor packages to the PX3TS:
1.
Connect a DPX2 sensor package to the first head connector of the
DPX2 sensor cable.
2.
Connect remaining DPX2 sensor packages to the second and then
the third head connector.
Tip: If the number of sensors you are connecting is less than the
number of head connectors on your sensor cable, connect them to
the first one or first two head connectors to ensure that there are NO
free head connectors prior to the final DPX2 sensor package
attached.
3.
Use an RJ-12 to RJ-45 adapter to connect the DPX2 sensor
package(s) to the PX3TS.
a.
Connect the adapter's RJ-12 connector to the DPX2 sensor
cable.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...