Chapter 3: Initial Installation and Configuration
33
Extended Cascading with PX3TS-iX7 Models
Only PX3TS-iX7 supports cascading via either Ethernet or USB ports
because they have two Ethernet ports and two USB-A ports.
You can use either Ethernet port on the iX7
™
device for cascading.
You must set the cascading mode before establishing the chain. See
Setting the Cascading Mode
(on page 282).
Both cascading modes support a maximum of 16 devices in a chain.
When establishing a Port-Forwarding chain, make sure you follow the
guidelines described in the section titled
Unsupported Cascading
Connections for Port Forwarding
(on page 36).
You can mix Ethernet and USB cascading in an iX7
™
chain if preferred.
The following diagram illustrates such a chain.
The distance between two Ethernet-cascaded devices can be up to 100
meters, while the distance between two USB-cascaded devices supports
up to 5 meters only.