![Raritan PX3TS User Manual Download Page 220](http://html1.mh-extra.com/html/raritan/px3ts/px3ts_user-manual_3996566220.webp)
Chapter 6: Using the Web Interface
196
Type a new value in the accompanying text box.
For concepts of thresholds, deassertion hysteresis and assertion
timeout, see
Sensor Threshold Settings
(on page 761).
6.
Click Save.
Setting Outlet Power-On Sequence and Delay
By default, outlets are sequentially powered on in the ascending order
from outlet 1 to the final when turning ON or power cycling all outlets on
the PX3TS device. You can change the order in which the outlets power
ON. This is useful when there is a specific order in which some IT
equipment should be powered up first.
In addition, you can make a delay occur between two outlets that are
turned on consecutively. For example, if the power-on sequence is Outlet
1 through Outlet 8, and you want the PX3TS to wait for 5 seconds after
turning on Outlet 3 before turning on Outlet 4, assign a delay of 5
seconds to Outlet 3.
To set the outlet power-on sequence:
1.
On the Outlets page, click
> Sequence Setup.
2.
Select one or multiple outlets by clicking them one by one in the
'Outlet' column.
3.
Click the arrow buttons to change the outlet positions.
Button
Function
Top
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...