Chapter 6: Using the Web Interface
199
Load Shedding Mode
When a UPS supplying power to the PX3TS switches into battery backup
operation, it may be desirable to switch off non-critical outlets to
conserve UPS battery life. This feature is known as load shedding.
Outlets that are turned off when load shedding is activated are called
non-critical outlets. Outlets that are not affected by load shedding are
called critical outlets. By default, all outlets are critical. To set
non-critical ones, see
Setting Non-Critical Outlets
(on page 197).
When load shedding is activated, the PX3TS turns off all non-critical
outlets. When load shedding is deactivated, the PX3TS turns back on all
non-critical outlets that were ON before entering the load shedding
mode.
Activation of load shedding can be accomplished using the web interface,
SNMP or CLI, or triggered by the contact closure sensors.
Note: It is highly suggested to check non-critical outlets prior to
manually entering the load shedding mode. The non-critical information
can be retrieved from the Outlets page. See
Outlets
(on page 190) or
Available Data of the Outlets Overview Page
(on page 194).
You must have the following two permissions to perform the load
shedding commands.
'Change Pdu, Inlet, Outlet & Overcurrent Protector Configuration'
'Switch Outlet' permission for all non-critical outlets
To enter the load shedding mode:
1.
On the Outlets page, click
> Activate Load Shedding.
Note: In case the PX3TS prevents you from performing this
command, check your permissions, especially if you have the Switch
Outlet permission for ALL non-critical outlets.
2.
Click Activate on the confirmation message.
In the load shedding mode:
The lock icon
appears for all non-critical outlets on the
Outlets page, and you CANNOT turn on any of them.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...