Enabling or Disabling Data Logging
This command enables or disables the data logging feature.
config:#
pdu dataRetrieval <option>
Variables:
<option> is one of the options:
enable or disable.
Option
Description
enable
Enables the data logging feature.
disable Disables
the
data logging feature.
For more information, see
Setting Data Logging
(on page 386).
Setting Data Logging Measurements Per Entry
This command defines the number of measurements accumulated per
log entry.
config:#
pdu measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60
samples per log entry.
For more information, see
Setting Data Logging
(on page 386).