Chapter 6: Using the Web Interface
185
Time Units
If you choose to type a new value in the time-related fields, such as the
Inrush Guard Delay field, you must add a time unit after the numeric
value. For example, you can type '15 s' for 15 seconds.
Note that different fields have different range of valid values.
Time units:
Unit
Time
ms millisecond(s)
s second(s)
min minute(s)
h hour(s)
d day(s)
Setting Thresholds for Total Active Energy or Power
Thresholds for total active energy and total active power are disabled by
default. You can enable and set them so that you are alerted when the
total active energy or total active power hits a certain level.
For a regular PX3TS model with multiple inlets:
Total active energy = sum of all inlets' active energy values
Total active power = sum of all inlets' active power values
To configure thresholds for total active energy and/or power:
1.
Click PDU.
On the PDU page, you can also view the total active power and
total active energy. See
PDU
(on page 176).
2.
Click the Thresholds title bar at the bottom of the page to display
thresholds.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...