Chapter 6: Using the Web Interface
205
To retrieve the exact data at a particular time, hover your mouse
over the data line in the chart. Both the time and data are
displayed as illustrated below.
To configure this outlet's threshold settings:
Per default, there are pre-defined RMS voltage and current threshold
values in related fields. See
Default Voltage and Current Thresholds
(on page 769). You can modify the defaults as needed.
Note: The threshold values set for an individual outlet will override the
bulk threshold values, if any, stored on that particular outlet. See
Bulk
Configuration for Outlet Thresholds
(on page 195).
1.
If the outlet's threshold data is invisible, click the Thresholds title
bar to display it.
2.
Click the desired sensor (required), and then click Edit Thresholds.