Chapter 3: Initial Installation and Configuration
39
All internal sensors become "unavailable", including sensors of
inlets, outlets, and OCPs.
Exception: Only active energy data remains available.
Communications with relay/meter boards are lost. Therefore,
firmware upgrade may fail due to this reason.
Available data or operations on the PDU that enters the
power-sharing mode:
Change software settings, such as customizing names, modifying
network settings, configuring thresholds, and so on.
Note: Outlet switching is not available because all outlets lose
power.
Monitor the status of connected Raritan environmental sensor
packages, or configure/control their settings.
Operate the front panel display.
Events that occur when entering the power-sharing mode:
The 12V power supply sensor enters the fault state. See
Transfer
Switch and Inlet Status
(on page 169).
Tip: You can set an event rule for sending a notification when this
sensor enters the fault state. See
Event Rules and Actions
(on page
The above event is logged in the internal event log. See
Default Log
Messages
(on page 336).
To find whether an iX7
™
has entered the power-sharing mode:
Check the state of its +12V power supply sensor.
Making a Power-Sharing Connection
Make sure BOTH iX7
™
devices comply with the configuration limitations
when establishing a power-sharing connection. See
Power-Sharing
Configurations and Restrictions
(on page 40).
The supported maximum power-sharing distance is 2 meters.
Make a power-sharing connection:
1.
Get a standard network patch cable (Cat5e/6), which can be up to 2
meters long.
Do NOT use a crossover cable.
2.
Connect one end to an iX7
™
device's EXPANSION port, and the other
end to another one's EXPANSION port.
Summary of Contents for PX3TS
Page 5: ......
Page 16: ...Contents xvii Index 807...
Page 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Page 85: ...Chapter 4 Connecting External Equipment Optional 61...
Page 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Page 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Page 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Page 792: ...Appendix I Additional PX3TS Information 768...