3-5
Section
Changing Numeral and Character String Display
313
PT Status Control (word n + 3)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
0
Controlled Item
Screen display
Processing priority registration (for NT link (1:N))
Continuous buzzer
Intermittent buzzer (short)
Display history initialization
Not used
Intermittent buzzer (long)
Backlight mode
Screen printing
PT window opening
Numeral/character string input
PT screen switching
Memory table copy execution
Memory table copy type
Alarm history initialization
Not used
1 (ON)
Performed
Registered
Sounded
Sounded
Performed
Sounded
Lit
Performed
Disabled
Disabled
Disabled
Performed
Numeral
Performed
0 (OFF)
Not performed
Canceled
Stopped
Stopped
Not performed
Stopped
Flashing
Not performed
Enabled
Enabled
Enabled
Not performed
Character string
Not performed
Always 0
Always 0
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Bits 2 and 3 are not used when the PT is in NT30/620
compatible mode.
Operate the PT status control area in the manner shown below to copy data be-
tween memory tables.
1, 2, 3...
1. Write the memory table numbers in the PT status control area as indicated
below in either 4-digit BCD or 4-digit hexadecimal. Which of the BCD and
hexadecimal notations is used is determined by the setting for PT Configu-
ration – Storage Type made at the Support Tool.
•
2nd word from the beginning (word n + 1)
0000 to 1999: Copy source memory table No. (0 to 1999)
•
3rd word from the beginning (word n + 2)
0000 to 1999: Copy destination memory table No. (0 to 1999)
Reference:
The range of numeral/character string memory table numbers which can actually
be used depends on the number of numeral memory tables and the character
string tables set in PT Configuration – System setting at the Support Tool.
2. Set bit 2 of the 4th word (word n + 3) from the beginning of the PT status
control area as indicated below to match the type of memory table for which
copying is to be executed.
Memory table type: Bit 2
•
Character string memory table: 0 (OFF)
•
Numeral memory table:
1 (ON)
3. Set 1 (ON) for bit 3 of the 4th word (word n + 3) from the beginning of the PT
status control area.
Data copy is executed between the specified type and specified numbers of
memory tables. If the copy destination table is allocated to a word in the host,
the contents at the word in the host are also changed. Then, the occurrence
of a change in the contents of the memory table is notified to the PT status
notify area.
electronic components distributor
Summary of Contents for NT21 Series
Page 3: ...iv Downloaded from Elcodis com electronic components distributor...
Page 5: ...vi Downloaded from Elcodis com electronic components distributor...
Page 463: ...Downloaded from Elcodis com electronic components distributor...
Page 465: ...Downloaded from Elcodis com electronic components distributor...