Appendix C
NT30/620 Compatible Mode
442
Item
NT30/620 compatible mode used
NT30/620 compatible mode not used
PT status
control
area
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word n
Word n+1
Word n+2
Word n+3
Screen number (4 BCD digits)
Copy type
PT status control bits
0
Copy source memory table number (3 BCD digits)
Copy destination memory table number (3 BCD digits)
Bit
Word
Word configuration
Word n is used to specify the screen switch setting only.
Word n+4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word n
Word n+1
Word n+2
Word n+3
Bit
Word
Screen number (4 BCD or hexadecimal digits)
Copy source memory table number (4 BCD or hexadecimal digits)
Copy destination memory table number (4 BCD or hexadecimal digits)
PT status control bits
Reserved for system use
Word configuration
Word n is used to specify the screen switch setting only.
PT status control bits
Word
Controlled Item
1 (ON)
0 (OFF)
15
Screen display
Performed
Not performed
14
Processing priority registration
Registered
Canceled
13
Continuous buzzer
Sounded
Stopped
12
Intermittent buzzer (short)
Sounded
Stopped
11
Display history initialization
Performed
Not performed
10
Not used
Always 0
9
Intermittent buzzer (long)
Sounded
Stopped
8
Backlight mode
Lit
Flashing
7
Screen printing
Performed
Not performed
6
PT window opening
Disabled
Enabled
5
Numeral/character string input
Disabled
Enabled
4
PT screen switching
Disabled
Enabled
3
Not used
*2
Always 0
2
Not used
*2
Always 0
1
Alarm history initialization
Performed
Not performed
0
Not used
Always 0
*1: Both the display history and alarm history are initialized when bit
11 is turned ON.
*2: Bits 2 and 3 are not used in NT30/620 compatible mode.
PT status control bits
Word
Controlled Item
1 (ON)
0 (OFF)
15
Screen display
Performed
Not performed
14
Processing priority registration
Registered
Canceled
13
Continuous buzzer
Sounded
Stopped
12
Intermittent buzzer (short)
Sounded
Stopped
11
Display history initialization
Performed
Not performed
10
Not used
Always 0
9
Intermittent buzzer (long)
Sounded
Stopped
8
Backlight mode
Lit
Flashing
7
Screen printing
Performed
Not performed
6
PT window opening
Disabled
Enabled
5
Numeral/character string input
Disabled
Enabled
4
PT screen switching
Disabled
Enabled
3
Memory table copy execution Performed
Not performed
2
Memory table copy type
Numeral
Character string
1
Alarm history initialization
Performed
Not performed
0
Not used
Always 0
Reflected in bit unit
PT status
notify area
Bit
Screen number (4 BCD digits)
Numeral/character string memory table number (4 BCD digits)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word m
Word m+1
Word m+2
Word
0
0
0
PT status notify bits
Word configuration
Word m is used for screen number notification.
(The function of the PT status notify bits does not change.)
PT status notify bits
0
0
0
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word m
Word m+1
Word
Numeral/character string memory table number
(BCD or hexadecimal 4 digits)
Word configuration
Screen number notification occurs in word n of the PT status control
area.
(The function of the PT status notify bits does not change.)
Image
codes
FE20 to FEFF hexadecimal, 224 codes max.
0001 to 0FFF hexadecimal, 4,095 codes max.
Library
codes
FA20 to FAFF, FB20 to FBFF, FC20 to FCFF, and FD20 to FDFF
hexadecimal, 896 codes max.
1000 to 3FFF hexadecimal, 12,288 codes max.
Insertion of
codes in
strings
Image and library codes
can
be inserted in character strings.
Image and library codes
cannot
be inserted in character strings.
Scrolling
alarm list
and history
The size and color from the earlier PTs can be used as-is. (Editing is
not possible.)
The size and color are changed to NT31/NT31C or NT631/NT631C
defaults. (Editing is not possible.)
electronic components distributor
Summary of Contents for NT21 Series