Processing Priority Registration (For NT Link 1:N) (Bit 14)
One of the PTs connected by the NT link (1:N) method can be registered for
priority processing. The PT for which bit 14 is set to ON (1) is given priority over
the other PTs, and has more rapid response time for screen display, touch switch
operations, etc.
When bit 14 is set to OFF (0), this registration is canceled and the response
speed is returned to normal. If priority registration is set for more than one PT, the
one set last is given priority.
The unit number of the PT given priority registration can be checked by monitor-
ing (reading) a word at the CS1G/CS1H, C200HX/HG/HE(-Z)E, CQM1H, and
SRM1. For details on the word monitoring operation at a PC, refer to the manual
for the PC you are using.
The contents of the words that reflect the status of an NT link (1:N) system are
indicated below.
Word
Bit
Function
〈
C200HX/HG/HE(-Z)E
〉
IR 265 (standard port)
IR 284 (port A)
*1
0
Communication in progress flag of unit No. 0:
ON when connected
IR 284 (port A)
*1
IR 285 (port B)
*1
1
Communication in progress flag of unit No. 1:
ON when connected
〈
CS1G/CS1H
〉
AR 393 (RS-232C port)
AR 394 (peripheral port)
2
Communication in progress flag of unit No. 2:
ON when connected
AR 394 (peripheral port)
CIO 1909 (port1)
*2
CIO 1919 (port2)
*2
CIO n+9 (port1)
*3
3
Communication in progress flag of unit No. 3:
ON when connected
CIO n+9 (port1)
*3
CIO n+19 (port2)
*3
〈
〉
4
Communication in progress flag of unit No. 4:
ON when connected
〈
CQM1H
〉
IR 202 (port 1)
*2
IR 203 (port 2)
*2
5
Communication in progress flag of unit No. 5:
ON when connected
IR 203 ( ort 2)
2
〈
SRM1
〉
AR 09
6
Communication in progress flag of unit No. 6:
ON when connected
AR 09
7
Communication in progress flag of unit No. 7:
ON when connected
8
Priority registration flag of unit No. 0: ON when priority given
9
Priority registration flag of unit No. 1: ON when priority given
10
Priority registration flag of unit No. 2: ON when priority given
11
Priority registration flag of unit No. 3: ON when priority given
12
Priority registration flag of unit No. 4: ON when priority given
13
Priority registration flag of unit No. 5: ON when priority given
14
Priority registration flag of unit No. 6: ON when priority given
15
Priority registration flag of unit No. 7: ON when priority given
*1: Communication board ports
*2: Ports on the Serial Communications Board
*3: Ports on the Serial Communications Unit (n=1500
)
25
the Unit’s unit number)
Continuous Buzzer (Bit 13), Short Intermittent Buzzer (Bit 12), Long Inter-
mittent Buzzer (Bit 9)
The continuous buzzer continues buzzing with no interruptions.
The short intermittent buzzer repeatedly alternates between sounding for 0.5
seconds and stopping for 0.5 seconds.
The long intermittent buzzer repeatedly alternates between sounding for 1.0 se-
conds and stopping for 1.0 seconds.
electronic components distributor
Summary of Contents for NT21 Series
Page 3: ...iv Downloaded from Elcodis com electronic components distributor...
Page 5: ...vi Downloaded from Elcodis com electronic components distributor...
Page 463: ...Downloaded from Elcodis com electronic components distributor...
Page 465: ...Downloaded from Elcodis com electronic components distributor...