manualshive.com logo in svg
background image

Artisan Technology Group 

is your source for quality 

new and certified-used/pre-owned equipment

• 

FAST SHIPPING AND 

DELIVERY

• 

TENS OF THOUSANDS OF 

IN-STOCK ITEMS

•  EQUIPMENT DEMOS
• 

HUNDREDS OF 

MANUFACTURERS 

SUPPORTED

•  LEASING/MONTHLY

 

RENTALS

•  ITAR CERTIFIED

           

SECURE ASSET 

SOLUTIONS

SERVICE CENTER REPAIRS

Experienced engineers and technicians on staff 

at our full-service, in-house repair center

WE BUY USED EQUIPMENT

Sell your excess, underutilized, and idle used equipment 

We also offer credit for buy-backs and trade-ins

www.artisantg.com/WeBuyEquipment

                        

REMOTE INSPECTION

Remotely inspect equipment before purchasing with 

our interactive website at

 

www.instraview.com

LOOKING FOR MORE INFORMATION? 

Visit us on the web at

 

www.artisantg.com

    

for more 

information on price quotations, drivers, technical 

specifications, manuals, and documentation

Contact us:

 

 

(888) 88-SOURCE  |  [email protected]  |  www.artisantg.com

SM

View

Instra

Содержание PanelView 1200 Series

Страница 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Страница 2: ...PanelViewt1200 Operator Terminals Catalog Numbers 2711 KA1 KC1 TA1 TC1 TA4 TC4 User Manual Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 3: ...Allen Bradley Company with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permis...

Страница 4: ...s 1 5 Touch Screen Terminal for Simplicity and Space Saving 1 5 Message and Alarm Handling Utilities 1 5 Built in Clock 1 6 Audio and Visual Feedback 1 6 Alarm Relay 1 6 RS 232 Port 1 6 PanelView 1200...

Страница 5: ...r Faults 2 2 Power Up Functions 2 3 Checksum and Read Write Memory Tests 2 3 Battery Failure Test 2 4 Communication Test 2 5 Watchdog Test 2 5 Starting Up the Terminal in Configuration Mode 2 5 The Co...

Страница 6: ...ls 2711 TA1 TC1 3 13 Touch Screen Terminals 2711 TA4 TC4 3 14 Optional Clip or Stud Rack Mount Kits 3 15 Remote Keyswitch Assembly Dimensions 3 16 Upload Download Cable 3 16 Verifying the PanelView 12...

Страница 7: ...e A 8 Storage Temperature Limits A 8 Humidity A 8 Maximum Altitude A 8 Monochrome Terminals A 8 Heat Generation A 8 Color Terminals A 8 Shock Amplitudes A 9 Shock and Vibration A 9 Vibration Amplitude...

Страница 8: ...n File A PanelView 1200 terminal application file contains a series of screens and configurations which when interpreted and executed by PanelView 1200 replace the functions of a control panel of butt...

Страница 9: ...the terminal s power cycle For example when a maintained push button is pressed the corresponding PLC input is set to 1 and will not change until the button is pressed a second time Retentive objects...

Страница 10: ...O Scanner Distribution Panel 1772 2 18 1775 S4A I O Scanner Programmer Interface Module User s Manual 1775 6 5 1 1775 S5 1775 SR5 I O Scanner Communication Adapter Module User s Manual 1775 6 5 5 5150...

Страница 11: ...Outside USA and Canada contact your local Allen Bradley office or call USA 216 646 6800 Your terminal s catalog number series revision letter and firmware revision are shown on the label on the back...

Страница 12: ...te PanelView 1200 terminal screens and functions See the PanelBuilder Development Software User Manual for information on PanelBuilder Development Software for DOS See the PanelBuilder 1200 Configurat...

Страница 13: ...ip Set Series C and earlier For application file back up or extra application RAM Series C and earlier logic boards 2711 NM2 Rack Mount Kit for Touch Screen Terminals To rack mount TA1 and TC1 termina...

Страница 14: ...This enables you to standardize on PanelView 1200 terminals thereby simplifying service stock and reducing the cost and time required to train your personnel on many different products Cost Optimized...

Страница 15: ...terminals can also communicate to the SLC 5 02 controller through the use of the 1747 SN module Direct or Data Highway Plus and Remote I O Downloading Application files can be downloaded from the dev...

Страница 16: ...red these terminals require less panel space Message and Alarm Handling Utilities A PanelView 1200 terminal application can be set up with stored messages that can be triggered by the PLC controller T...

Страница 17: ...e PLC controller to activate the beeper at the terminal allow Alarm Messages to activate the beeper at the terminal Alarm Relay You can attach a horn or a warning light to the PanelView 1200 terminal...

Страница 18: ...the PanelView 1200 terminal s RS 232 Port You use it to transfer applications serially between the development computer and the PanelView 1200 terminal If you have a number of terminals you may want t...

Страница 19: ...als certain screen objects are specific to keypad terminals others to touch screen terminals For more information on objects see your PanelBuilder 1200 Configuration Software for Windows User Manual o...

Страница 20: ...they can perform a wide variety of functions ranging from turning on PLC input bits to changing screens Keys can have different functions for each screen created Numeric Keypad The keypad terminal has...

Страница 21: ...e and Lower are used with Numeric Input Cursor Points only The three blank keys at the bottom right are reserved for future development and are not configurable For more details see your PanelBuilder...

Страница 22: ...tions are listed in three groups those used on both keypad and touch screen terminals those used for keypad terminals only and those used for touch screen terminals only You will note that the objects...

Страница 23: ...reen Selector Static Touch Screen Multistate Indicator Dynamic Both List Indicator Dynamic Both Set Value Button Dynamic Both Increment Value Button Dynamic Both Decrement Value Button Dynamic Both Nu...

Страница 24: ...tly selected option Control List Selector with Enter contains a vertical list of operator choices An operator can use the object s Up Cursor and Down Cursor buttons to move an arrow through the availa...

Страница 25: ...w you to assign display attributes to four possible states for each symbol object The symbols have two sizes large and small Bar Graphs can be used to monitor changing conditions such as temperature o...

Страница 26: ...are graphic objects like lines which can surround other objects or simply illustrate Arcs are used to illustrate quarter semi and three quarter circles as well as circles They can also be used to con...

Страница 27: ...or enters is stored at this address The keypad is available in large and small sizes The Information and Alarm Windows can pop up on the screen at any time to display important information Information...

Страница 28: ...hange always has precedence over operator controlled screen changes and operator generated screen changes are allowed only if the PLC address contains 0 PLC Controlled Screen Print allows the PLC cont...

Страница 29: ...230 4K baud with any PLC 5 capable of supporting that baud rate If you are using a PLC 5 15 with partial rack addressing and block transfers you must use PLC 5 15 series B revision J or later PLC 5 1...

Страница 30: ...SN I O Subscanner Module Refer to the 1771 SN Sub I O Scanner Module Data Sheet for specific details 6008 SI IBM PC I O Scanner This module can be installed in an IBM PCr or compatible computer to pr...

Страница 31: ...ng illustration shows the rear panel of a PanelView 1200 terminal Note the location of the Mode Select Keyswitch the brightness control Monochrome terminals and the contrast control Color terminals Fi...

Страница 32: ...e the faults logged to the Major Fault Window cannot be cleared If the terminal is set to Configuration mode the Major Faults detected on power up will be logged to the Minor Fault Window and can be c...

Страница 33: ...depending on the Mode Select Keyswitch setting Important If an application file is in battery backed RAM and a user memory PROM containing a different application file has been installed the applicati...

Страница 34: ...ry should fail a Minor Fault message will appear to inform the operator As long as the terminal s power is not turned off there is no problem If power is lost and restored to the terminal the results...

Страница 35: ...this test it is a major fault and the terminal will require servicing by Allen Bradley To start up your PanelView 1200 terminal in Configuration mode set the Mode Select Keyswitch to Configure and con...

Страница 36: ...de Menu for a touch screen terminal also contains a False Depression Test which is discussed later in this chapter Upload Download There are two methods of uploading and downloading application files...

Страница 37: ...ode menu by cursoring to Serial Port and pressing ENTER 2 Press the Choose List button The list of parameters in the window on the left will toggle between these headings Upload Download to configure...

Страница 38: ...for uploading and downloading For printer settings refer to your printer s manual Rack Assignments Choose Rack Assignments to view the rack assignments and block transfer file definitions of the curre...

Страница 39: ...n a touch screen terminal 23733 SECURITY ACCESS CODES Save Exit ENT DEL 7 8 9 4 5 6 1 2 3 0 CLR Security Off Security On Next Operator Operator Number 1 Access Code 0000 To set an operator s code on a...

Страница 40: ...e alarm messages and the PLC Controlled Audio operation the Audio Volume level to High or Low The default setting is High Alarm Relay The alarm relay can be wired to an external alarm or warning light...

Страница 41: ...Presets For more information on retentive objects see your PanelBuilder Development Software User Manual or your PanelBuilder 1200 Configuration Software for Windows User Manual Power up Values can be...

Страница 42: ...ew 1200 terminal screen by blanking the screen when no buttons have been pressed for a period of time Choose Screen Saver from the Configuration Mode menu to display the screen and set the amount of t...

Страница 43: ...e function key nearest the Save Exit button saves the current screen alignment and returns you to the Configuration Mode Menu The following illustration shows the Screen Alignment screen for a keypad...

Страница 44: ...before the terminal determines that it the key or cell is stuck and enters fault mode Use the keypad to set the amount of time from 0 to 99 seconds A setting of 0 disables the function False Depressio...

Страница 45: ...t screen 20226 FALSE DEPRESSION TEST Exit False Depressions Last Cell Detected User EPROM EEPROM Power Up Test PanelView 1200 terminals include a socket for an optional user PROM If your terminal does...

Страница 46: ...10801 Bytes Used 52175 Bytes Free CONFIGURATION MODE MENU Down Cursor Enter Upload Download Serial Port Rack Assignments Access Codes Audio Response Alarm Relay Preset Operations Time and Date Screen...

Страница 47: ...s Choosing Manual Address Source will disable the Terminal s current application file Select Application to enable 23662 PASS THROUGH DOWNLOAD OPTIONS Auto Restart Address Source PLC Type BAUD Rate Ra...

Страница 48: ...it Important On the keypad terminal when Rack Number is selected and you press the Change Data button a keypad window opens This window disappears when you enter a valid rack number On the touch scree...

Страница 49: ...s Through Address Source If the application file contains a pass through configuration its values are displayed in the Manual Address Source area If the application file does not contain a pass throug...

Страница 50: ...ass Through The Starting Module Rack Size and Last Chassis parameters enable you to assign the terminal as one of the racks already configured in the PLC scan list When replacing an existing PanelView...

Страница 51: ...l s display panel Attention Loss of power during this test could result in loss of the application data stored in battery backed memory If this occurs you will have to repeat the downloading process D...

Страница 52: ...is occupied by the Exit button Each cell is tested by pressing it If the cell is working it changes to normal then back to reverse video when pressed a second time The following illustration shows th...

Страница 53: ...en it is switched to Run mode and the Address Source is Application When the Address Source is Manual the PanelView 1200 terminal will show the Download in Progress screen when it is switched to Run m...

Страница 54: ...m The Application Data Checksum test periodically checks the application file in battery backed RAM If the PanelView 1200 terminal fails this test the terminal enters Major Fault mode You will need to...

Страница 55: ...lready printing a screen In the case of PLC controlled screen prints the PLC can be informed that the printer is busy when the PLC sends the print message in PanelBuilder software enable Screen Print...

Страница 56: ...errors can t be indicated to the terminal directly The terminal can detect a print error only if the hardware or software handshaking is enabled and the appropriate serial lines are connected from the...

Страница 57: ...how to connect an external alarm relay how to connect your PanelView 1200 terminal to your PLC system how to install the optional user PROM the PanelView 1200 terminal dimensions the cutout dimension...

Страница 58: ...ort connects the PanelView 1200 terminal to the development computer for uploading and downloading application files and connects the PanelView 1200 terminal to a serial printer You can also connect t...

Страница 59: ...200 terminal can be used to trigger a remote alarm or warning light under specific conditions You would attach this remote alarm or light to the Alarm Relay as shown in the following figure Figure 1 3...

Страница 60: ...rate for 57 6 kilobaud and 115 2 kilobaud use a 150W resistor A B part 740018 29 for 230 kilobaud use an 82W resistor A B part 740018 23 Figure 1 4 Remote I O Connector 20163 2 SHIELD 1 The AC Power C...

Страница 61: ...e the PanelBuilder Development Software User Manual or the PanelBuilder 1200 Configuration Software for Windows User Manual Attention Make sure the power cable is disconnected before you open a PanelV...

Страница 62: ...ics don t move too much or scuff your feet when walking on carpets be extra careful in low humidity environments 4 Open up the PanelView 1200 terminal logic drawer Remove the two screws located near t...

Страница 63: ...nals require one PROM to achieve the same functionality PanelView 1200 terminals prior to Series D that have had the logic board replaced may also require only one PROM depending on the revision of th...

Страница 64: ...e properly positioned Attention If you break or severely bend a pin the chip will be unusable 9 Close the PanelView 1200 terminal and fasten the screws then reconnect the Remote I O cable RS 232 cable...

Страница 65: ...imensions of the keypad and touch screen terminals Refer to these diagrams when mounting your terminal Figure 1 9 Monochrome Keypad Terminal Dimensions 21167 12 40 314 96 mm 0 250 6 35 mm 11 66 296 16...

Страница 66: ...ower F21 F20 F19 F18 F17 F16 F8 F15 F7 F14 F6 F13 F5 F12 F4 F11 F3 F10 F2 F9 F1 13 97 354 84 mm 19 00 482 6 mm 0 585 14 86 mm 0 400 10 16 mm PanelView A A Color Keypad Figure 1 11 Monochrome Touch Scr...

Страница 67: ...closure to compress this gasket The gasket has built in spacers that will not allow it to be over compressed You will notice that the tightening torque increases significantly when you reach the corre...

Страница 68: ...e modification to T30 panel cutout for keypad terminals Figure 1 13 Keypad Terminal Panel Cutout CUTOUT C C L C L C L 1 50 38 1mm 5 50 139 70mm 1 50 5 50 6 70 6 70 170 18mm L 4 35 110 49mm 4 35 8 70 2...

Страница 69: ...CUTOUT C L 6 425 163 2mm 1 08 27 43mm 7 32 5 56mm DIA TYP 18 PLACES MOUNTING STUDS ARE 10 32 SIZE 6 425 1 08 Touch Screen Terminals 2711 TA1 TC1 The following diagram shows the clip mount touch screen...

Страница 70: ...C4 Figure 1 17 Stud Mount Touch Screen Terminal Panel Cutout C C L 6 35 161 29 mm L 4 30 109 22 mm 21181 CUTOUT 13 00 330 2 mm 12 50 317 5 mm 6 24 158 49 mm 2 05 12 50 317 5mm 13 11 333 mm 2 05 52 07m...

Страница 71: ...mm 19 00 482 6 mm 3 20 81 28 mm 1 48 37 6 mm 5 48 139 2 mm 8 48 215 4 mm 12 48 317 mm 13 97 354 84 mm 578 14 68 mm 278 7 06 mm 735 18 67 mm 75 19 05 mm C 125 3 18 mm Clip mount Figure 1 19 NR2 19 Rac...

Страница 72: ...3 000 76 2 mm 0 025 0 000 2 625 66 67 mm 0 64 mm 0 00 The Upload Download Cable is used to transfer an application file to or from a PanelView 1200 terminal As marked one end of the cable connects to...

Страница 73: ...e specially marked short cable to the computer end of the upload download cable This adapter will accommodate the slightly different pinout configuration found on this card Figure 1 21 Upload Download...

Страница 74: ...S CTS DSR COM DCD DTR 9 PIN FEMALE Development Sys 3 2 7 8 6 5 1 4 NC TXD RXD RTS CTS DSR COM DCD DTR Figure 1 23 Adapter Cable for 6121 Combo Adapter 2 option card 20221 25 PIN MALE Upload Download C...

Страница 75: ...figuration Mode Menu The Unit Tests screen appears The following figure shows the Unit Tests screen on a touch screen terminal The keypad screen is slightly different 20205 UNIT TESTS Battery Good Pre...

Страница 76: ...in the PanelBuilder software must be the same The factory settings of the PanelView 1200 terminal and the PanelBuilder software are matched If you have not changed them you can download the DEMO or y...

Страница 77: ...sage PLC communication lost You can safely ignore this message at this stage If the power up screen for your application file appears on your terminal your file has been successfully downloaded If you...

Страница 78: ...appens inside the PLC controller as you use each object and then change the values within the PLC controller to see how the PanelView 1200 terminal responds Switch the PanelView 1200 terminal to Confi...

Страница 79: ...tem testing Step through each screen to make sure that valid states and values are displayed Test each object one at a time to ensure that the PLC system responds as expected Power down then power up...

Страница 80: ...ater on a cotton gauze pad or soft cotton cloth Mild soap or detergent and warm water is also permissible but avoid abrasive cleaners Cleaning the Enclosure Use a 50 solution of alcohol ethanol or iso...

Страница 81: ...play the Screen Saver Timeout screen Here you set the amount of time that should pass without screen activity before the screen blanks Elapsed time can range from 1 to 999 minutes A setting of 0 zero...

Страница 82: ...sure the line transformer can handle this surge Strong Magnetic Fields Since the PanelView 1200 terminal display contains a CRT cathode ray tube the presence of strong magnetic fields near the termin...

Страница 83: ...1 TC4 Series E Touch Screen Terminals w Color CRT stud mount Standards Organizations Approvals UL listed Industrial Control Equipment UL 508 CSA certified standard 22 2 No 142 Design Standards Complie...

Страница 84: ...aled stainless steel dome membrane switches with tactile feedback and an actuation force of 16 oz 0 455 kg mounted on the key panel s anodized aluminum backer plate Keys are rated for 2 000 000 presse...

Страница 85: ...timeout Display Size 12 Diagonal Color Unit Display Attributes You select 8 from a palette of 16 colors Black Grey White Bright White Red Bright Red Blue Bright Blue Green Bright Green Magenta Bright...

Страница 86: ...ons Allen Bradley PLC via Allen Bradley 1771 Remote I O Link Remote I O baud rate 57 6 115 2 230 4 kilobaud max I O cable distance 10 000 ft 57 6 kilobaud 5 000 ft 115 2 kilobaud 2 500 ft 230 4 kiloba...

Страница 87: ...settings that the development software will apply to the selected RS 232 port on your development system so you normally shouldn t need to change them The factory defaults are as follows Port Paramete...

Страница 88: ...l supports 64K of standard user memory in battery backed RAM You can install an additional EPROM for application file back up You can install an additional EEPROM for either application file back up o...

Страница 89: ...ulations are based on battery life specifications provided by the battery manufacturer and does not take battery shelf life into account display modes AM PM or Military Hours minutes seconds date disp...

Страница 90: ...to 104 F 75 humidity 40 to 50 C 104 to 122 F 40 humidity Relative non operating humidity non condensing 40 to 70 C 40 to 158 F 95 humidity Maximum Altitude non operating 40 000 ft operating 10 000 ft...

Страница 91: ...cy range 5 to 2000 Hz 5 to 57 Hz 006 peak to peak displacement 58 to 2000 Hz 1 0 G peak acceleration Vibration Amplitudes for Non Operating Units Frequency range 5 to 2000 Hz 5 to 57 Hz 015 peak to pe...

Страница 92: ...rrupted Unit is disabled The ROM containing the system firmware is defective Servicing by Allen Bradley is required RAM TEST failed Unit is disabled The non backed up RAM used by the terminal firmware...

Страница 93: ...memory is dead Upload the application file and save it on disk Servicing by Allen Bradley is required Communication Self Test failed The communication card is defective or not installed Servicing by...

Страница 94: ...C Communication Lost when using 1772 SD2 scanner with PLC 2s Must use 1772 SD2 scanner Rev 3 or later Rapid blinking of PLC Communication Lost when using 1775 S4A scanner with a PLC 3 Must use 1775 S4...

Страница 95: ...communication lost appears at the top of the PanelView 1200 terminal screen Make sure the PLC 5 is in RUN mode and is configured to recognize the PanelView 1200 terminal on the remote I O link See Au...

Страница 96: ...Use the PLC 5 6200 Series software to clear the Minor Fault then reconfigure the PLC 5 to recognize the new rack assignment PLC Controllers Required for Pass Through Important Only specific models and...

Страница 97: ...or is shutdown PLC controller is faulted or PLC program is corrupted The cable is disconnected from the PLC controller The wrong PLC station address was specified Using PCMK card and the KL BIN files...

Страница 98: ...gher Ensure that the settings on the KT card match those entered in the Pass Through download configuration See the following table for information on selecting a memory location for the KT card 218 F...

Страница 99: ...LC Controlled 1 17 Audio Response Screen 2 10 Audio Volume 2 10 Auto Line Feed parameter 2 8 B Bar Graphs 1 14 Battery 1 4 A 7 Failure 2 24 Failure indications A 7 Failure test 2 4 Battery backed RAM...

Страница 100: ...tomatic 5 2 A 4 Diagnostic Testing on line 2 24 Diagnostics 1 7 Display ASCII 1 15 Date 1 14 Local Message 1 15 Numeric Data 1 14 Time 1 14 Display test 2 23 Downloading 1 4 4 2 Dynamic objects 1 11 E...

Страница 101: ...ad terminals A 1 Touch Screen terminals A 2 NEMA Standards A 1 Next Operator 2 9 Non Printable Characters 2 26 Numeric Data Display 1 14 Numeric Input Cursor Point 1 15 Numeric Keypad 1 16 Numeric Key...

Страница 102: ...List without Enter 1 13 Keypad Screen 1 16 Screen List 1 13 Serial Communications Port A 5 Serial Port 2 7 Serial printer 3 2 Set Bit Cursor Point 1 16 Set Value Button 1 14 Shock Amplitudes A 9 Sile...

Страница 103: ...Index I 5 W Watchdog Circuit 2 5 Test 2 5 Window P 3 Alarm 1 16 Information 1 16 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 104: ...ds Turkey United Arab Emirates United Kingdom United States Uruguay Venezuela Yugoslavia World Headquarters Allen Bradley 1201 South Second Street Milwaukee WI 53204 USA Tel 1 414 382 2000 Fax 1 414 3...

Страница 105: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Отзывы: