![Omron NT21 Series Reference Manual Download Page 324](http://html1.mh-extra.com/html/omron/nt21-series/nt21-series_reference-manual_744543324.webp)
3-5
Section
Changing Numeral and Character String Display
315
PC Program
Make a PC ladder program as shown below.
Copy destination memory table No.
Copy destination word
(1)
Copy source memory table No.
Copy source word
Copy type, copy destination memory table No.
Copy destination word
(2)
Copy source memory table No.
Copy source word
@MOV(21)
#0004
102
@MOV(21)
#0010
101
09000
Error flag
@ORW(35)
#0008
103
103
TIM
001
#0010
(1.0S)
@ANDW(34)
#FFF7
103
103
TIM001
@MOV(21)
#0004
102
@MOV(21)
#0011
101
09000
Error flag
@ORW(35)
#0008
103
103
TIM
002
#0010
(1.0S)
@ANDW(34)
#FFF7
103
103
TIM002
Copy type, memory table copy execution bit
Word of PT status control bits
Memory table copy execution bit set from 1 to 0
Copy type, memory table copy execution bit
Word of PT status control bits
Memory table copy execution bit set from 1 to 0
Program Operation
1, 2, 3...
1. If an error occurs (bit 09000 goes ON), the display on the PT changes to
FAULT.
2. When the error is eliminated (bit 09000 goes OFF), the display on the PT
returns to NORMAL.
Changing Numerals/Character Strings by Pressing a Touch Switch Which Has the
Copy Setting Function
This method allows an operator to change the contents of a memory table simply
by operation at the PT. It is also possible to copy data to a numeral setting/char-
acter string input field by using this method. With the Copy Setting function, data
can only be copied in accordance with the predetermined method.
electronic components distributor
Summary of Contents for NT21 Series
Page 3: ...iv Downloaded from Elcodis com electronic components distributor...
Page 5: ...vi Downloaded from Elcodis com electronic components distributor...
Page 463: ...Downloaded from Elcodis com electronic components distributor...
Page 465: ...Downloaded from Elcodis com electronic components distributor...