Inputting Numeric Values
185
Settings
Table Entry
Number of the numeral memory table into which the input
numeric value is written
Range: 0 to 1999
Display Type
Display format for the numeric value (Input numeric value
and stored data, page 186)
Decimal/Hexadecimal
Format (Number of digits displayed, page 185)
Integer
Number of digits in the integer part of
the numeric value
Range: 1 to 10
Maximum
combined total of
Decimal
Number of digits in the decimal
fraction of the numeric value
Range: 0 to 9
combined total of
10 digits
Limit (Upper/lower (max./min.) limit check, page 188)
Maximum
Upper limit for numeric values that can be input
Minimum
Lower limit for numeric values that can be input
Zero Suppression
Whether or not zero suppression is used (Zero
suppression, page 134)
Check mark (zero suppression used)/
No check mark (zero suppression not used)
Display Sign
Whether or not negative numbers are indicated (setting
ineffective if Hexadecimal has been set for Display Format)
(Input numeric value and stored data, page 186)
Check mark (negative numbers indicated)/
No check mark (negative numbers not indicated)
Focus Frame
Presence/absence of a frame indicating that the numeral
setting input field has become ready to accept input
Check mark (frame present)/
No check mark (frame not present)
Focus Attribute
Display status before the input numeric value is confirmed
(Display attributes and drawing result, page 190)
Standard/Inverse/Flash/Inverse Flash
Interlock Function
Interlock
Presence/absence of interlock control of numeral input
Check mark (interlock)/No check mark (don’t interlock)
PC address settings
PC bit address
Allocated interlock bit used to enable/disable operation of
the numeral input (See Interlock Bit Allocation on page
189.)
I/O comments
Comment that explains the allocated bit.
Up to 16 characters.
Background color
123456
Position
Foreground color
Number of Digits Displayed
All contents of numeral memory tables are stored as integers. To display a nu-
meric value that has a decimal fraction in a numeral setting input field, set the
Decimal setting to 1 or higher to specify the number of places after the decimal
point. A decimal point is then automatically inserted.
electronic components distributor
Summary of Contents for NT21 Series
Page 3: ...iv Downloaded from Elcodis com electronic components distributor...
Page 5: ...vi Downloaded from Elcodis com electronic components distributor...
Page 463: ...Downloaded from Elcodis com electronic components distributor...
Page 465: ...Downloaded from Elcodis com electronic components distributor...