This means that flow = 0 is going to output a mA signal in the middle of the
measurement span.
Example:
4 mA
= -100 l/s
20 mA
= 100 l/s
In this case the signal output is 12 mA if flow = 0. Backwater will cause the ana-
log signal to decrease, positive flow will cause the signal to increase.
Error mode
This parameter is to define the desired analog output condition if an error (such
as cable break, CPU failure or similar) should occur.
Pressing this key will select between the following functions:
-
0 mA
-
hold (will hold the latest valid signal value until the error has been removed
or the error is no longer existent)
-
4 mA or
-
20.5 mA
8.5.5 Parameter Menu „Digital Outputs“
Fig. 8-31
Digital outputs – submenu
This menu allows to define both functions as well as accompanying parameters
(such as limit values, duration of impulse and more) of individual relay outputs.
Channel number
Select from relays 1–5 which one is to be set by using the following parameters.
Name
This menu is visible only if a function has been enabled. The menu name refers
to the name of the relay output selected before. It is not required to enter a
name here as it currently is used for internal unit functions only.
The procedure is the same as described in >PAR/Measurement Place/Name of
Measurement Place<.