39
5.0
System Limits
5.1
FleX-Net™ System Limits
Unless otherwise noted, these limits apply to software and firmware version 12.2.33.
Table 3 FleX-Net™ System Limits
Device
Maximum number
Nodes
63 per system
CPUs
15 per node: 1 on the main board + 7 local per node (quad
loop adders and 1 audio controller) + 7 remote per node
(annunciators)
128 CPUs in total per system
Note: The Configurator treats LED annunciators as having
CPUs.
Remote Annunciators
7 LCD annunciators per node or 4 LED annunciators per node
A maximum of 7 annunciators in total per node
50 annunciators per system
Quad Loop Adders
7 per node
Built-in Conventional Loops
2 per node
128 per system
Addressable Loops
29 per node (7 quad loop adders with 4 loops each + 1 built-in
loop)
Addressable Sensors
159 per loop
Addressable Input/Output Modules
159 per loop
Audio Controllers
1 per node
Amplifiers
3 adder bins per node: maximum number of amplifiers: 25
25 60-Watt amplifiers per node
or
50 30-Watt amplifiers per node
or
100 15-Watt amplifiers per node
Zone Switches
250 per system
Page Select Switches
504 per system
Telephone Select Switches
504 per system
Inputs correlated to Remote Zones
1800 per CPU
Remote Output Zones
1800 per CPU
UDACTs
1 per system