154
Using the Configurator
5. Click
Add
.
The Configurator adds the display adder.
If the frame limit for the annunciator you are adding to is exceeded, an error message
appears. A frame is a measure of display capacity. See
LT-894 FleX-Net™ Installation
and Operation Manual
for information about how many frames each annunciator has
available, and how many frames each display adder uses.
6. Click
Close
.
View the display adder
•
Select
Display Adder
in the Job Tree.
Table 27 describes the columns in the display adder view.
Table 27 Display Adders
Name
Description
Idx
The zero based position of the item on the adder.
Unnamed
Linked Item - contains an asterisk if the item shares the same LedGrp with
other items. This means that correlations to one such item are added to all
linked items. Linked Items can be created when Paste Special is used. The
linked items can be viewed with the Linked Items dialog.
Type
The type of display item.
Assignment
Dependent on the Type.
Node Group
Applies only to common control switches. The column displays the Node
Group to which the common control operation is to be limited. Global
means that the operation is system wide and is the default. If the user has
created Node Groups, then one of those groups can be chosen. The
common control then applies only to the member nodes of that group.
Priority
Specifies the priority to be given to digitized messages correlated to
correlatable switches. Choose from a range or priorities.
í
19 (lowest)
through Normal (default) to +19 (Highest). Activation of a switch with a
higher priority will cause its message to be played, and any lower priority
message will cease to play.
In a combined fire and Mass Notification System (MNS) installation,
choose appropriate priorities. For example, if risk analysis has determined
that MNS has priority over fire, assign a higher priority to all MNS digitized
message switches. Within MNS relative priorities can be set, so that higher
priority messages will have precedence over lower priority messages.
Code
If the Type is Zone Switch and Coded System is specified, then Code is
displayed and editable as for an Input Circuit.
F1
If the item is a switch, then this column can be set to ER (enable required),
meaning that it requires a passcode.
F2
For bypass and manual switches, this column can be set to AR (Aux Reset
Required). For correlatable switches it can be set to NS (non-silenceable)
F3
For correlatable switches this column can contain GA (stage two, general
alarm device). For bypass and manual push switches, it can be set to SR
(System Reset Required).