Using the Configurator
See the Network Node Details
•
Select a node in the Job Tree.
Figure 109 Network Node Details
Alternate Ground Fault
Detection
If you select this check box, the system will use alternate
ground fault detection settings to compensate for the
capacitance and resistance of long audio cable runs. See
section 12.5 on page 88.
Two Stage
Check to enable two stage.
As per UL 864 and UL 2572 only a setting of Single Stage
(disabled) is permissible.
Day Light Savings
Daylight savings is configured on the Job Details screen
(section 19.5 on page 134).