Using the Configurator
201
•
SR
: System Reset required - for switches used for fan control.
•
NF:
No LED Activation - do not turn ON an addressable device’s LED (and activate
sounder when present) when the device is active. The LED turns ON by default and may
only be changed to NF if the Authority Having Jurisdiction allows.
•
HV
: High Volume - use the High Volume setting on an AP sounder base.
Sens Columns
Sensitivity level for COSAP provides 6 levels of sensitivity, which are categorized as below:
•
Alarm 1:
Level 1 - 1%/ft of smoke. No delays from processed photo output.
•
Alarm 2:
Level 2 - 2%/ft of smoke. No delays from processed photo output.
•
Alarm 3:
Level 3 - 3%/ft of smoke. No delays from processed photo output.
•
Alarm 4:
Level 4 - 3%/ft of smoke. Maximum of 10 minutes delay from processed photo
output.
•
Alarm 5:
Level 5 - 4%/ft of smoke. Maximum of 10 minutes delay from processed photo
output.
•
Alarm 6:
Level 6 - Heat only alarm. If the heat level limits.
Once the CO cell has reached its end of life, and enters PTIR mode, the following sensitivities
apply:
•
Alarm 1:
Level 1 - 1%/ft of smoke. No delays from processed photo output.
•
Alarm 2:
Level 2 - 2%/ft of smoke. No delays from processed photo output.
•
Alarm 5:
Level 5 - 3%/ft of smoke. Time elapsed from smoke detection is
•
Alarm 6:
Level 6 - Heat only alarm. If the heat level on either thermistor exceeds 1 limits.
•
CO Operation:
CO only alarm.
19.51 Fire Phone Configuration
You can set up an audio controller, conventional phones, voice lines, remote field phones,
master telephone handsets and telephone selectors, and you can connect them together.
You need at least an Audio Network Controller Module (ANC-5000), a Telephone Network
Controller Module (TNC-5000), a Telephone Master Controller (QMT-5302N(V)), and a
Telephone/Page Selector (QAZT-5302DS or QAZT-5348DS). The Audio Controller supports
conventional fire phone circuits or voice lines. There may also be addressable fire phone
modules. If you configure addressable fire phone modules you must also ensure that there is a
voice line to support them.
19.51.1 Adding an audio controller
•
See section 19.24 on page 171 for instructions on adding an audio controller.
The Audio Network Controller Module (ANC-5000) must have a Telephone Network Controller
Module (TNC-5000) installed.
Note:
Your organization needs audio systems training in order to add an audio
controller to a job. To check whether you have this training, see section 2.9 on
page 22.