32
Upgrading Firmware
3.3
Connecting to the System
Now that you have the appropriate Configurator, as well as the matching job file, you can
connect to the panel to update the firmware.
Connect to the system
1. Insert your CodeMeter key into the computer.
2. Connect the USB cable to the UIMA4 cable.
3. Connect the 10-pin head of the UIMA4 cable to the last CPU in the CPU chain that starts
from the main board.
Figure 24 Connect to P3 on FX-2000N Series Panels
Figure 25 Connect to P3 on ALCN-792MISO Loop Controller
Figure 26 Connect to P10 on ANC-5000
Note:
The port is P3 on the FleX-Net™ main board and ALCN-792MISO, P4 on
ALC-386S, and P10 on ANC-5000.
i
Computer
UIMA4 interface
USB A to B male cable
USB connector 10 pin connector
P3 on main board
P3
Computer
USB A to B male cable
UIMA4 interface
P3 on ALCN-792MISO
USB connector 10 pin connector
+ - + -
S S
+ - + -
ALARM OUT
B
A
A
B
COM (-)
P3
Computer
UIMA4 interface
USB A to B male cable
P10 on ANC-5000
USB connector 10 pin connector
P10