50
Custom Timers and Intervals
5. Select
Trouble Zone 1
.
6. Click
the
Advanced Logic
tab at the bottom, and then click
Edit
.
The
Advanced Logic Editor
appears.
7. Click
the
NOT
button.
8. Select the interval you created, and then click the
>
button to move the interval to the
Equation box.
9. Click
the
EQU
button.
10. Click the pulldown menu, click
INTVL_ACTIVE
, and then click the
Sys_Def
button.
The equation should look like this:
NOT **-**-**-IT-010 EQU INTVL_ACTIVE
11. Type a description in the
Description
box, and then type a comment in the
Comments
box.
12. Click
OK
to close the
Advanced Logic Editor
.
13. Right-click the zone, then click
Add Correlations
.
14. Add an output, and then click
Close
.
Trouble Zone 1
will become active when the current time is not within the interval.
If you want the zone to become active when the current time is within the interval, omit
NOT
from the equation.
DoW
Day of the week. This is optional. If you leave it blank, then the
interval applies every day.
Tag