Hardware Layouts
69
11.7.4
BB-5008 Fire Node Backbox
The BB-5008 backbox is larger than the BBX-1072A(R)DS. It can use the FX-2009-12NDS
Large Main Chassis combined with ECX-0012 Expander Chassis (see section 11.7.6 on
page 71) for additional display modules and the CCH-5008ANNUNKIT/PANELKIT and CCH-
5014ANNUNKIT/PANELKIT Custom Mounting Kits for paging and fire fighter telephone
modules. The FX-2009-12NDS Large Main Chassis can be substituted for two ECX-0012
Expander Chassis with the main display being replaced by the DSPL-420 Narrow Main
Display module. The outer dimensions of the BB-5008 fit within 38.0” X 32.5” X 7.5”. See
Figure 46 and Table 16.
Table 16 BB-5008 Backbox
Name
Description
Holds
Number of
Displays and
Remote
Annunciators
Dimensions
BB-5008
Lobby Control
Backbox
1 FX-2009-
12NDS or 2
ECX-0012s
DSPL-420
DSPL-2440
RAXN-LCD
RAXN-LCDG
QMT-5302N
QMP-5101N
QAZT-5302DS
QAZT-5348DS
INX-10AC
24 Ah battery
pack
8 (the FX-2009-
12NDS uses 4,
the ECX-0012
uses 2)
38.0” H x 32.5” W