46
Walk Test
4. Right-click the walk test area, and then select
Add Input Devices
.
Figure 41 Add Input Devices
The
Select items to add
window appears.
Figure 42 Select items to add
5. Select the input devices that you want to add to this walk test area, and then click
Add
.
6. Click
Close
.
7. Repeat these steps for each walk test area.
7.2
Configuring the Walk Test Switch
You can configure a switch as a walk test switch. Press the walk test switch to access the walk
test menu.
Configure the Walk Test Switch
•
In the Display Adder view of the Main Display or 24 Sw Adder, set a switch to the Type
Common Ctrl
and the Assignment
Walk Test Sw
.
Figure 43 Walk test switch