196
Using the Configurator
Flag Columns
There are up to 5
Flag
columns (F1, F2, F3, F4, and F5) for flags of various types.
NS
: Non Silenceable - used on inputs and supervised outputs.
GA
: Stage two alarm - in a two stage system.
ND
: No Display - This zone will not appear in the alarm queue.
CO
: CO Alarm - This indicates a carbon monoxide detection zone. Sounder bases correlated
to this zone will sound the corresponding CO pattern. It can be set for zone Type
Supv.
or
Alarm
.
SA
: Zone activation - This is equivalent to cancelling Signal Silence. It can be set only for zone
Type
Supv.
or
Mon
.
19.48 Output Groups
Output groups let you specify a group of Advanced Protocol relay modules, control modules,
and sounder bases that you want to activate simultaneously.
FleX-Net™ uses the Advanced Protocol broadcast command to simultaneously activate all
relay modules, control modules, and sounder bases that are in the same output group when
there is a general alarm or fire drill.
In order to configure output devices so that they activate simultaneously when they are
triggered by an input, you must correlate the output devices to an input zone in addition to
adding the output devices to an output group.
19.48.1 Add Output Devices to an Output Group
1. Click
Output Groups
in the Job Tree under
Base I/O
.
2. Click
Insert
in the menu bar, then click
Add Groups
.
Figure 158 Add Output Group
3. In the Device menu, select
Output Group
.
Note:
You can only add devices that are on the same CPU to an output group. For
example, you cannot add devices from both Node 1 and Node 2 to the same
output group. However, you can add devices from more than one loop on a quad
loop adder to the same output group.
i