AP Reports
37
The numbers are the analog values retrieved from sub-addresses in the device. For most
devices, the usual value for the first sub-address is 50, which indicates that the device is in a
normal state.
4.3
AP Group Param
Use this report to check the output group configuration (see section 19.48 on page 196). The
report prints the output group numbers for every device. A device can be in four output groups.
The value
0
does not indicate any particular output group.
Figure 33 AP Group Param report
In Figure 33, the photo detector is correlated to a relay base and the relay base is part of
output group 1. This device is in only 1 output group (the remaining 3 output groups are 0).
The unsupervised output module is part of output group 2. This device is in only 1 output
group (the remaining 3 output groups are 0).
4.4
AP Param List
Generate this report when requested by technical support.
This report prints the complete list of the internal non-volatile parameters of the devices. It
contains the device type, OEM value, output groups, and other useful information.
Figure 34 AP Param List report
Figure 34 shows the printed report from an SLC with two configured devices.
The second and third numbers after the device’s description are the OEM value and the Type
(as described in tables 1 and 2). The device with the
Photo Detector
description is Type
023
(Photo) and OEM value
011
(Secutron).
The second device is described as a
Unsupv Output Module
(relay). However the actual
device is shown as Type
163
(Control). If the device really was an unsupervised output
module, the Type would
164
(Relay). The OEM value is
003
(Mircom).