Using the Configurator
169
Add a correlation to an item
1. Right-click the item in the Details Pane.
2. Click
Add Correlations
.
The
Select items to add
window appears.
3. Double-click the correlations that you want to add, and then click
Close
.
Output Circuit Correlations
If the selected circuits are outputs, then the Correlations Pane usually has tabs for:
•
Alarm Zones
•
Supervisory Zones
•
Trouble Zones
•
Monitor Zones
•
Display Points (Output Zones, Bypass LEDs, etc.)
Input Circuit Correlations
If the selected circuits are inputs, then the Correlations Pane has a tab for input zones only.
You must correlate inputs with input zones before they can be correlated to outputs or LEDs.
When you select an item and then click
Add Correlations
, only the items that are eligible to
be correlated are shown.
If you select multiple items and then click
Add Correlations
, only the possible correlations
common to all the items are shown.
Advanced Logic
You can assign individual outputs or input zones to an equation. If an equation is associated
with an output, there must be no other inputs or outputs correlated to the output. If an equation
is associated with an input zone, there must be no input circuits correlated to the input zone.
19.23 Custom Messages
Custom messages are messages that you can correlate with a zone or zone switch. The
messages appear on a remote annunciator.
For example, for a facility with a main display in the Exhibit Hall and a remote annunciator in
the East Wing:
•
The devices are displayed individually on the main display.