152
Using the Configurator
19.8.1
Passcodes
This section appears on the main display only.
Figure 113 Passcodes
Set or change the passcodes
•
Type the passcodes for three levels of access. Passcodes must consist of the digits
0
,
1
,
2
, and
3
only.
On the main display, the queue buttons function as passcode buttons:
•
ALARM
: 0
•
SUPV
: 1
•
TROUBLE
: 2
•
MONITOR
: 3
Enter a passcode on the main display
1. Press the queue buttons corresponding to the numbers. For example, to enter the
passcode
2222
, press the
TROUBLE QUEUE
button 4 times.
2. Press
the
ENTER
button.
19.8.2
Main Display
There are three types of Main Display supported on the FleX-Net™ panel.
Change the type of main display
1. Select the type of main display in the
Type
menu.
2. Click
Yes
.
19.8.3
Access Levels
Specify the level of access for various panel actions.
•
0
means that the panel operator does not need to enter a passcode.
Table 26 Displays
Name
Name in the Configurator
DSPL-420-16TZDS
4x20 C/W 16 LED
DSPL-420 or DSPL-420DS
4x20 (Default)
DSPL-2440
24x40 Graphic