Using the Configurator
135
Options
Two stage
Select this check box to configure the system as a two
stage system. If you do not select this, then the system is
single stage.
As per UL 864 and UL 2572 only a setting of Single Stage
(disabled) is permissible.
Fire drill
Select this check box to enable the panel's Fire Drill
switch.
Manual signal silence
Select this check box to enable the panel's Signal Silence
switch.
Style D (Class A) Conv
Inputs
Select this check box to indicate that the panel has Style
D (Class A) conventional inputs.
Style D (Class A) Input
Modules
Select this check box to indicate that input modules' field
wiring is Style D (Class A).
Style 6 and 7 (Class A) Loop
Select this check box to indicate that the panel has Style 6
and 7 (Class A) addressable loops.
Style Z (Class A) Fire Phone
Select this check box to indicate that the wiring from an
addressable fire phone module and the handset is Style Z
(Class A).
Style 7 (Class A) Network
Select this check box to indicate that the wiring between
Network Nodes is Style 7 (Class A).
Digital Audio
Select this check box to indicate that the audio signals
use the ARCNet wiring between network nodes. If this
option is not selected, then the audio runs over a separate
pair of wires.
Digital Phone
Select this check box to indicate that the fire phones use
the ARCNet wiring between network nodes. If this option
is not selected, then the phones communicate over the
telephone bus terminals.
Single Trouble Bypass
Setting this option will suppress troubles for ALL signal
output circuits. Only the Signal Bypass switch active
trouble will be generated by bypassing from a switch on a
DSPL or IPS-2424 or IPS-4848DS.
Silence NAC Audibles Only
If this check box is selected, all Alarm, Supervisory,
Trouble, and Monitor zones with the NS flag will silence
only audible signals when signal silence is activated.
Disable Waterflow Retard
If this check box is selected, the retard timer for waterflow
devices is disabled. The purpose of this check box is to
accommodate sprinkler systems that already have a built-
in waterflow retard timer.
Subsequent Alarms: ONLY
in Separate Zones
If this check box is not selected, then upon activation of a
subsequent alarm for any device in any zone, the signals
will re-sound. If this check box is selected, then upon
activation of a subsequent alarm for only a device in a
different zone, the signals will re-sound.
Monitor alert
Select this check box to make an alert sound play when a
monitor input activates.