198
Using the Configurator
19.48.2 Correlate Output Devices to an Input Zone
In order to configure output devices so that they activate simultaneously when they are
triggered by an input, you must also correlate the output devices to an input zone.
1. Select the input zone that you want to add the output devices to.
2. Click
Insert
in the menu bar, then click
Add Correlations
.
The
Select items to add
window appears.
Figure 160 Select items to add to input zone
3. Select
the
Signal
tab for Control (AP) and Sounder Base (AP) devices, and select the
Relay
tab for Relay (AP) devices.
4. Select the same output devices that you added to the output group in section 19.48.1. To
select more than one device, hold down the Ctrl key and click the devices.
5. Click
Add
.
6. Click
Close
.
Note:
The list of outputs in the output group must match the list of outputs
correlated to the input zone.
If the input zone contains more outputs than are in
the output group, then the outputs that are not in the output group will not activate
simultaneously when they are triggered by the input. However, if the output group
contains more outputs than are in the input zone, then no outputs will activate
simultaneously.
For example, consider a job that contains 10 output devices. If all 10 devices are
correlated to an input zone, and the output group contains only 5 devices, then
only the 5 devices in the output group will activate simultaneously when they are
triggered by the input.
If the output group contains all 10 devices, but only 5 of these devices are
correlated to an input zone, then no devices will activate simultaneously when
they are triggered by the input.