Using the Configurator
155
19.11 UDACT
A UDACT (Universal Digital Alarm Communicator/Transmitter) is a device that communicates
alarms to a central monitoring station using the Contact ID or SIA communication formats.
The dialer can dial out on two phone lines. You must configure an account and specify the line
attributes for both. Line 2 can dial a cell phone. If this is the case the auto test can be reduced
from daily to monthly.
Add a UDACT
1. Select the node that you want to add a UDACT to.
2. Click
Insert
in the menu bar, then click
Add UDACT
.
The
Add UDACT
window appears.
Figure 116 Add UDACT
3. Select
Contact ID
,
SIA300
or
SIA110
in the
Report Format
menu.
4. Select
Auto Assign
if you want to assign a UDACT group of the correct type to every
input zone and output circuit.
5. Click
Add
.
F4
The CR flag lets you define which switches are locked when Node Control
Enable is selected. If the CR flag is not set, then the switch is always
unlocked.
The CR flag on a switch with the Type
Common Ctrl
is propagated to all
other occurrences of the same switch in the network. For example, if you
set the CR flag on the System Reset switch on one display adder, all
System Reset switches in the network automatically have the CR flag.
Switches that are not
Common Ctrl
switches are not propagated. For
example, a paging switch or a bypass switch can be configured to require
control on one node, but to always allow operation on a different node,
regardless of which node has control.
Tag 1
Except for Common Controls, System Status and Man Ena, a 20 character
tag can be entered. It will be used to identify the control in messages. For
some Type/Assignment combinations the tag cannot be edited.
Tag 2
Correlatable Switches (being analogous to Input Zones) accept a second
line of 20 characters.
Table 27 Display Adders (Continued)
Name
Description