2.4 SDI Output Mapping
In this menu you have the option, to configure the Data-Broker-
Mapping for the SDI.
Here you can specify up to four different register areas (start address
and number of successive registers) as data sources.
Optionally, you can activate a timeout and specify default data that
should be valid in the event of a timeout.
--------------------------------------------------
KUNBUS-IC -
SDI
Outputmapping
--------------------------------------------------
Src Register Number
1 - 1 (0x0001) | 0
2 - 1 (0x0001) | 0
3 - 1 (0x0001) | 0
4 - 1 (0x0001) | 0
5 - Default Data: all zero
6 - Valid Time: disabled
--------------------------------------------------
>
Configuring Output Mapping
--------------------------------------------------
KUNBUS-
IC
– Edit one map entry
--------------------------------------------------
Source Register:
ü
First determine the start address of the source register.
You can get an overview of the start addresses in the chapter Register
for the Mapping [
}
80].
◦ To do this, select a register from the input data area of the
communication channels and then enter the number of registers to be
used.
ð
After entering the number of registers, you will return automatically
to the mapping overview.
TIP: If you want the Data Broker to swap high and low bytes at the
same time as copying, you must add 0x8000 to the number of
registers.
◦ Restart the module.
ð
Your mapping is now configured and will be applied in the operating
mode.
--------------------------------------------------
KUNBUS-
IC
– Edit one map entry
--------------------------------------------------
Source Register: 0x1001
Number of Registers:
CDI