IC-Module for EtherNet/IP
62 / 137
0x0006 Set parity bits for the
SDI interface
In this memory register you have the option, to set the parity bit for
the data transmission of the SDI interface.
The number of stop bits is adjusted automatically to the parity to
ensure that a transmission always contains the same number of bits.
The new settings are applied after a reset.
Modbus Register
0x0006
Value Range
0x00-0x02
Default Value
0x00 (Even Parity)
Number of available
bytes
1
Permanently stored
Yes
Access
Read/Write
Meaning
0x0000
Even Parity, 1 Stop-Bit
0x0001
Odd Parity, 1 Stop-Bit
0x0002
No Parity, (2 Stop-Bits)
0x0007 Current bitrate of the
SDI interface
In this memory register you will find information about the currently
used bitrate of the SDI interface.
Modbus Register
0x0007
Value Range
0x0000-0x0007
Initial value
-
Number of bytes
available
1
Permanently stored
No
Access
Read Only
Meaning
0x0000
The bitrate is unknown or has not yet been
determined by the automatic bitrate detection.
0x0001
2400 bit/s
0x0002
4800 bit/s
0x0003
9600 bit/s
0x0004
19200 bit/s
0x0005
38400 bit/s
0x0006
57600 bit/s
0x0007
115200 bit/s
Memory Register