IC-Module for EtherNet/IP
72 / 137
0x0020 Module type
This register contains the unique identification number for the module
type of the KUNBUS-IC . This module type provides information
regarding which product type it is and which fieldbus the module is
used for.
Modbus Register
0x0020
Value Range
0x00-0xff
Initial value
8 or 56 (s. “Meaning”)
Number of available
bytes
1
Permanently stored
Yes
Access
Read Only
Meaning
8
IC Module with one Ethernet-Port
56
IC Module with two Ethernet-Ports
0x0021 Default values in the
data communication
configure
In this memory register you have the option, to specify the behaviour
of the memory register in case no data from outside is received
anymore on the SSC Modbus RTU or fieldbus interface.
Modbus Register
0 x 0021
Valid value range
0x00-0x3f
Default Value
0 x 00
Number of available
bytes
1
Permanently stored
Yes
Access
Read/Write
Meaning
Bit 1, Bit 0:
SS1 and SS0 (SSC interface)
00: Output data is set to 0 (default value)
01: Output data is set to 1
10: The data last written is retained
Bit 3, Bit 2:
FB1 and FB0 (fieldbus interface)
00: Output data is set to 0 (default value)
01: Output data is set to 1
10: The data last written is retained
Bit 5, Bit 4:
SD1 and SD0 (SDI interface, Modbus RTU)
00: Output data is set to 0 (default value)
01: Output data is set to 1
10: The data last written is retained
15 14
13 12 11 10
9
8
7
6
5
4
3
2
1
0
SD
SD
FB
FB
SS
SS
Memory Register