IC-Module for EtherNet/IP
61 / 137
0x0005 Set bitrate for the SDI
interface
In this memory register you have the option, to define with which
bitrate the SDI interface should communicate.
Automatic bitrate detection means that the module tests the following
bitrates until it has received a correct Modbus-RTU telegram:
• 2400 bit/s
• 4800 bit/s
• 9600 bit/s
• 19200 bit/s
• 38400 bit/s
• 57600 bit/s
• 115200 bit/s
NOTICE! During automatic bitrate detection the module does not
send a reply to the master until the correct bitrate has been
detected. This procedure can require up to 40 polls of the
master.
TIP: Set a fixed bitrate if the automatic bitrate detection lasts too
long for you.
The new settings are applied after a reset.
Modbus Register
0x0005
Value Range
0x00-0x07
Default Value
0x00
Number of available
bytes
1
Permanently stored
Yes
Access
Read/Write
Meaning
0x00
Automatic bitrate detection
0x01
2400 bit/s
0x02
4800 bit/s
0x03
9600 bit/s
0x04
19200 bit/s
0x05
38400 bit/s
0x06
57600 bit/s
0x07
115200 bit/s
Memory Register