IC-Module for EtherNet/IP
84 / 137
7.5 Fieldbus specific Registers
0x4001 Fieldbus Status
In this memory register you will find information about the current
communication status of the fieldbus interface.
This memory register contains a bitfield. Therefore, the values
described below can be added in the memory register.
Modbus Register
0x4001
Value Range
0x0001-0x2000
Number of available bytes
2
Permanently stored
No
Access
Read Only
Meaning
0x0001
Indicates that a link is available on a port
0x0002
Module is operational but has no data
connection
0x0004
There is a data connection and a cyclical
data exchange takes place.
0x0008
The cyclical data connection was ended
with a timeout.
0x1000
There is an address conflict
0x2000
A recoverable error has occurred
0x4004 Manufacturer Number
This Memory Register contains the manufacturer number. This can
be changed if necessary.
If you change manufacturer ID, you have to adjust the EDS file
accordingly.
Modbus Register
0x4004
Value Range
-
Default Value
1168
Number of Bytes
2
Permanently stored
Constant
Access
Read/Write
Memory Register