Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-63-
Note:
This kind of V/F curve separation can be applied in various frequency-conversion power
sources, however, you should be cautious of parameter setup as improper setup may damage the
machine.
Function
code
Name
Description
Default
value
P00.00
Speed control mode
0: Sensorless vector control (SVC) mode 0
1: SVC 1
2: SVPWM
3: FVC
Note:
To select 0, 1, or 3 as the control mode,
enable the VFD to perform motor parameter
autotuning first
2
P00.03 Max. output frequency P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.11
Acceleration time 1 0.0
–3600.0s
Depends
on model
P00.12
Deceleration time 1 0.0
–3600.0s
Depends
on model
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.02
Rated power of
asynchronous motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depends
on model
P04.00
V/F curve setting of
motor 1
0: Straight-type V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F (V/F separation)
0
P04.01
Torque boost of motor
1
0.0%: (automatic) 0.1%
–10.0%
0.0%
P04.02
Motor 1 torque boost
cut-off
0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.03
V/F frequency point 1
of motor 1
0.00Hz
–P04.05
0.00Hz
P04.04 V/F voltage point 1 of 0.0%
–110.0%
0.0%