Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-85-
Present reference
channel
P00.09
Multi-function terminal
function 13
Channel A switches to
channel B
Multi-function terminal
function 14
Combination setup
switches to channel A
Multi-function terminal
function 15
Combination setup
switches to channel B
B
A
/
/
A+B
/
A
B
A-B
/
A
B
Max (A, B)
/
A
B
Min (A, B)
/
A
B
Note: "/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and DOWN
(11), you can increase/decrease the frequency quickly by setting P08.45 (UP terminal frequency
incremental change rate) and P08.46 (DOWN terminal frequency decremental change rate).
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Function
code
Name
Description
Default
value
P00.03
Max. output frequency
P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.06
A frequency command
selection
0: Keypad
1: AI1
2: AI2
3: AI3
4: High speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
0
P00.07
B frequency command
selection
15