![INVT GD350-004G-4 Operation Manual Download Page 156](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703156.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-147-
Function
code
Name
Description
Default
value
Modify
P01.09
–P01.12).
Setting range of P01.29: 0.0
–150.0% (of the rated
VFD output current)
Setting range of P01.30: 0.0
–50.0s
Setting range of P01.31: 0.0
–50.0s
P01.32
Pre-exciting time
of jogging
0
–10.000s
0.000s
○
P01.33
Starting
frequency of
braking for
jogging to stop
0.00Hz
–P00.03
0.00Hz
○
P01.34
Delay to enter
sleep
0
–3600.0s
0.0s
○
P02
––
Parameters of motor 1
Function
code
Name
Description
Default
value
Modify
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
◎
P02.01
Rated power of
asynchronous
motor 1
0.1
–3000.0kW
Depends
on model
◎
P02.02
Rated frequency
of asynchronous
motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
◎
P02.03
Rated speed of
asynchronous
motor 1
1
–60000rpm
Depends
on model
◎
P02.04
Rated voltage of
asynchronous
motor 1
0
–1200V
Depends
on model
◎
P02.05
Rated current of
asynchronous
motor 1
0.8
–6000.0A
Depends
on model
◎
P02.06
Stator resistance
of asynchronous
motor 1
0.001
–65.535Ω
Depends
on model
○
P02.07
Rotor resistance
of asynchronous
0.001
–65.535Ω
Depends
on model
○