![INVT GD350-004G-4 Operation Manual Download Page 417](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703417.webp)
Goodrive350 series high-performance multifunction VFD
Optional peripheral accessories
-408-
Note:
Do not connect C3 filters in IT power systems.
Interference filters on the input side can reduce the VFD interference on the surrounding devices.
Noise filters on the output side can decrease the radio noise caused by the cables between VFDs and
motors and the leakage current of conducting wires.
INVT provides some of the filters for you to choose.
D.7.1 Filter model description
04
-
C
A
D
E
FLT
L
B
P
045
F
B
-
Field identifier
Field description
A
FLT: Name of the VFD filter series
B
Filter type
P: Power input filter
L: Output filter
C
Voltage class
04: AC 3PH 380V (-15%)
–440V (+10%)
06: AC 3PH 520V (-15%)
–690V (+10%)
D
3-digit code indicating the rated current. For example, 015 indicates 15A.
E
Filter performance
L: General
H: High-performance
F
Filter application environment
A: First environment (IEC61800-3), category C1 (EN 61800-3)
B: First environment (IEC61800-3), category C2 (EN 61800-3)
C: Second environment (IEC61800-3), category C3 (EN 61800-3)
D.7.2 Filter model selection
Table D
–11 AC 3PH 380V(-15%)–440V(+10%)
VFD model
Input filter
Output filter
GD350-1R5G-4
FLT-P04006L-B
FLT-L04006L-B
GD350-2R2G-4
GD350-004G-4
FLT-P04016L-B
FLT-L04016L-B
GD350-5R5G-4
GD350-7R5G-4
FLT-P04032L-B
FLT-L04032L-B
GD350-011G-4
GD350-015G-4
FLT-P04045L-B
FLT-L04045L-B
GD350-018G-4
GD350-022G-4
FLT-P04065L-B
FLT-L04065L-B
GD350-030G-4