Goodrive350 series high-performance multifunction VFD
Function parameter list
-178-
Function
code
Name
Description
Default
value
Modify
16: Value 1 set through
PROFIBUS/CANopen/DeviceNet communication
17: Value 2 set through
PROFIBUS/CANopen/DeviceNet communication
18: Value 1 set through Ethernet communication
19: Value 2 set through Ethernet communication
20: HDIB input
21: Value 1 set through
EtherCAT/PROFINET/EtherNet IP communication
22: Torque current (bipolar, 0
–Triple the motor
rated current)
23: Exciting current (bipolar, 0
–Triple the motor
rated current)
24: Set frequency (bipolar)
25: Ramp reference frequency (bipolar)
26: Rotational speed (bipolar)
27: Value 2 set through
EtherCAT/PROFINET/EtherNet IP communication
28: AO1 from the programmable card
29: AO2 from the programmable card
30: Rotational speed (100% corresponds to twice
the motor rated synchronous speed)
31: Output torque (Actual value, 100%
corresponds to twice the motor rated torque)
32: AI/AO temperature detection output
33
–63: Reserved
Note:
When the output comes from the programmable
card (28
–29), if the card is a Codesys
programmable card, P27.00 must be set to 1.
When AO1 is of the current output type, 100%
corresponds to 20mA; when AO1 is of the voltage
output type, 100% corresponds to 10V; 100% of
HDO corresponds to the output of P06.30.
P06.17
Lower limit of
AO1 output
Above function codes define the relation between
output value and analog output. When the output
value exceeds the set max./min. output range, the
upper/low limit of output will be adopted during
calculation.
0.0%
○
P06.18
Corresponding
AO1 output of
lower limit
0.00V
○