![INVT GD350-004G-4 Operation Manual Download Page 218](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703218.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-209-
Function
code
Name
Description
Default
value
Modify
mode.
When the fire mode has lasted 5 minutes, it is
reset, and no warranty of repair is processed.
P11.54
Running
frequency in fire
mode
0.00Hz
–P00.03 (Max. output frequency)
50.00Hz
○
P11.55
Fire mode flag
0
–1
Note:
When the fire mode has lasted 5 minutes, it
is reset, and no warranty of repair is processed.
0
●
P11.56
–
P11.69
Reserved
/
/
/
P12
––
Parameters of motor 2
Function
code
Name
Description
Default
value
Modify
P12.00
Type of motor 2
0: Asynchronous motor
1: Synchronous motor
0
◎
P12.01
Rated power of
asynchronous
motor 2
0.1
–3000.0kW
Depends
on model
◎
P12.02
Rated frequency
of asynchronous
motor 2
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
◎
P12.03
Rated speed of
asynchronous
motor 2
1
–60000rpm
Depends
on model
◎
P12.04
Rated voltage of
asynchronous
motor 2
0
–1200V
Depends
on model
◎
P12.05
Rated current of
asynchronous
motor 2
0.8
–6000.0A
Depends
on model
◎
P12.06
Stator resistance
of asynchronous
motor 2
0.001
–65.535Ω
Depends
on model
○
P12.07
Rotor resistance
of asynchronous
motor 2
0.001
–65.535Ω
Depends
on model
○
P12.08
Leakage
inductance of
0.1
–6553.5mH
Depends
on model
○