Goodrive350 series high-performance multifunction VFD
Function parameter list
-146-
Function
code
Name
Description
Default
value
Modify
P01.22
Waiting time of
restart after
power down
This parameter specifies the waiting time before
automatically running at next power-on after power
down.
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Setting range: 0.0
–3600.0s (valid when P01.21=1)
1.0s
○
P01.23
Start delay
This parameter specifies the delay of the VFD
’s
wake-up-from-sleep after running command is
given, the VFD will start to run and output after the
time set by P01.23 elapses to realize brake
release.
Setting range: 0.0
–600.0s
0.0s
○
P01.24 Stop speed delay 0.0
–600.0s
0.0s
○
P01.25
Open-loop 0Hz
output selection
0: No voltage output
1: With voltage output
2: Output as per DC braking current of stop
0
○
P01.26
Deceleration time
of
emergency-stop
0.0
–60.0s
2.0s
○
P01.27
Time of starting
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.28
Time of ending
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.29
Short-circuit
braking current
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
enter short-circuit brake.
During stop, if the running frequency of VFD is
below the starting frequency of braking after stop,
set P01.31 to a non-zero value to enter
short-circuit braking after stop, and then carry out
DC braking in the time set by P01.12 (refer to
0.0%
○
P01.30
Hold time of
short-circuit
braking at startup
0.00s
○
P01.31
Hold time of
short-circuit
braking at stop
0.00s
○