Goodrive350 series high-performance multifunction VFD
Troubleshooting
-288-
Fault
code
Fault type
Possible cause
Corrective measures
E-BAC
[67] BACNet card
communication
timeout fault
There is no data
transmission between the
communication card and the
host controller (or PLC).
Check whether the
communication card wiring is
loose or dropped
E-DEV
[68] DeviceNet card
communication
timeout fault
There is no data
transmission between the
communication card and the
host controller (or PLC).
Check whether the
communication card wiring is
loose or dropped
SECAN
[58] CAN
master/slave
communication card
communication
timeout fault
There is no data
transmission between the
CAN master and slave
communication cards
Check whether the
communication card wiring is
loose or dropped
S-Err
[69] CAN slave fault
in master/slave
synchronization
Fault occurred to one of the
CAN slave VFDs
Detect the CAN slave VFD and
analyze the corresponding fault
cause of the VFD
P-E1
–
P-E10
[45]
–[54]
Programmable card
customized faults 1
–
10
User program logic error in
the programmable card.
A fault occurred on the
customized position.
Check the user program logic.
Perform troubleshooting based
on actual customized faults.
OtE1
[70] EC PT100
detected OH
The PT100 temperature
sensor is inaccurate or not
calibrated.
Device or ambient
temperature is too high.
Calibrate the sensor through
parameter settings.
Lower the device or ambient
temperature.
OtE2
[71] EC PT1000
detected OH
The PT1000 temperature
sensor is inaccurate or not
calibrated.
Device or ambient
temperature is too high.
Calibrate the sensor through
parameter settings.
Lower the device or ambient
temperature.
E-EIP
[72] EtherNet IP
communication
timeout
There is no data
transmission between the
communication card and the
host controller (or PLC).
Check whether the
communication card wiring is
loose or dropped.
E-PAO
[73]
No upgrade
bootloader
The upgrade bootloader is
missing.
Contact us.
E-AI1
[74] AI1
disconnection
Input voltage of AI1 is too
low;
AI1 wiring is disconnected.
Connect a 5V or 10mA power
source to check whether the
input is normal;
Check the wiring or replace the
cables.