Goodrive350 series high-performance multifunction VFD
Function parameter list
-238-
Function
code
Name
Description
Default
value
Modify
0: Forward
1: Reverse
Hundreds: CD/UVW pole signal direction
0: Forward
1: Reverse
P20.03
Detection time of
encoder offline
fault
The detection time of encoder offline fault.
Setting range: 0.0
–10.0s
Note:
When the value is 0.0s, the fault will not be
detected.
2.0s
○
P20.04
Detection time of
encoder reversal
fault
Detection time of encoder reversal fault.
Setting range: 0.0
–100.0s
0.8s
○
P20.05
Filter times of
encoder
detection
Setting range: 0x00
–0x99
Ones: Low-speed filter time, corresponds to 2^(0
–
9)×125
μs.
Tens: High-speed filter times, corresponds to2^(0
–
9)×125
μs.
0x33
○
P20.06
Speed ratio
between encoder
mounting shaft
and motor
You need to set this parameter when the encoder
is not installed on the motor shaft and the drive
ratio is not 1.
Setting range: 0.001
–65.535
1.000
○
P20.07
Control
parameters of
synchronous
motor
0x0000
–0xFFFF
Bit0: Enable Z pulse calibration
Bit1: Enable encoder angle calibration
Bit2: Enable SVC speed measurement
Bit3: Reserved
Bit4: Reserved
Bit5: Reserved
Bit6: Enable CD signal calibration
Bit7: Reserved
Bit8: Do not detect encoder fault during autotuning
Bit9: Enable Z pulse detection optimization
Bit10: Enable initial Z pulse calibration optimization
Bit11: Reserved
Bit12: Clear Z pulse arrival signal after stop
Bit13: Reserved
Bit14: Detect Z pulse after one rotation
Bit15: Reserved
0x0003
○