Goodrive350 series high-performance multifunction VFD
Function parameter list
-206-
Function
code
Name
Description
Default
value
Modify
during
overvoltage stall
Setting range: 0
–1000
P11.22
Integral
coefficient of
voltage regulator
during
overvoltage stall
This parameter is used to set the integral
coefficient of the bus voltage regulator during
overvoltage stall.
Setting range: 0
–1000
10
○
P11.23
Proportional
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0
–1000
60
○
P11.24
Integral
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the integral
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0
–2000
250
○
P11.25
Enable VFD
overload integral
0: Disabled
1: Enabled
When this parameter is set to 0, the overload
timing value is reset to zero after the VFD is
stopped. In this case, the determination of VFD
overload takes more time, and therefore the
effective protection over the VFD is weakened.
When this parameter is set to 1, the overload
timing value is not reset, and the overload timing
value is accumulative. In this case, the
determination of VFD overload takes less time,
and therefore the protection over the VFD can be
performed more quickly.
0
◎
P11.26
Reserved
/
/
/
P11.27
VF vibration
control method
0x00
–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0
–1: Reserved
0x00
◎
P11.28
SPO detection 0.0
–60.0s
5.0s
○